In terms of fuel tank:
1.The end of the oil tank higher than 50mm, so as not to precipitate inhaled diesel generator.
2.The tank must have air vents, and vent the need to prevent dust and water into the tank.
3.The tank bottom should be extra Sheng diesel oil pan to collect the overflow, or discharge of oil in the tank next to the open ditch to drain the overflow diesel.
4.tank top view should bring the mouth to facilitate the repair of.
Tubing for delivery:
1.should be black iron pipe delivery pipe damage due to chemical reaction of diesel generator sets, can not use galvanized pipe.
2.The 25mm diameter delivery pipeline to 32mm, the unit is less than 800KVA by 25mm, the unit is greater than 800KVA with 32mm.
3.and diesel generators to send tubing connection between the hose connection must be used to isolate the vibration generator.
On the return pipe:
1.Send pipeline dimensions and materials used in the same return line with the diesel generator connection between the hose connection must be to isolate the vibration generator.
2.the oil pressure is limited, the oil return pipe to the tank must be kept at 2.5 m height difference below.